Industrial heat pump for simultaneous heating & cooling applications
Our ChillHeat heat pumps offer a wide range of optimized solutions for various industrial applications. All our ChillHeat products are designed and manufactured in Finland and rigorously tested at the desired operating conditions before being shipped out, ensuring optimal performance and reliability. Our R&D department and Product Development Process (PDP) ensure product quality and reliability through meticulous testing. ChillHeat heat pumps can be connected in parallel for higher capacity heating or cooling solutions. A versatile automation system is a key feature of all our ChillHeat products, enabling energy-efficient and user-friendly operation. Few applications are:
- Combined heating and cooling
- Waste heat recovery at refrigeration plants (ammonia, HFC, CO2)
- Heat recovery from wastewater
- Ground source heating
- Flue gas heat recovery
- Heat recovery from industrial processes (evaporators, cooling towers, driers)
- Heat extraction from outdoor air
- Water chiller applications
Oilon ChillHeat RE110 – RE420
Oilon ChillHeat RE series heat pumps are best suited for heating and cooling large residential buildings and industrial plants.
- Max. hot water temperature 63 °C
- Combined cooling and heating
- Large residential buildings 10,000-20,000 m² or industrial process
Description/Model | RE100 | RE140 | RE170 | RE210 | RE330 | RE420 | |
---|---|---|---|---|---|---|---|
No. of Compressors compressor type |
2 scroll |
2 scroll |
2 scroll |
2 scroll |
3 scroll |
4 scroll |
|
Refrigerant | R410A | R410A | R410A | R410A | R410A | R410A | |
Heat output, kW (ground source heating) |
EN 14511 0/35 °C |
107 | 134 | 168 | 205 | 308 | 410 |
COP | EN 14511 0/35 °C |
3.7 | 3.6 | 3.7 | 4.2 | 4.2 | 4.2 |
Heat output, kW (heating network) |
18/8 °C 40/55 °C |
136 | 168 | 208 | 272 | 409 | 546 |
COP | 18/8 °C 40/55 °C |
2.8 | 2.8 | 2.8 | 3.6 | 3.6 | 3.6 |
Cooling output, kW (air conditioning) |
12/7 °C 36/42 °C |
103 | 128 | 158 | 209 | 314 | 418 |
COPc | 12/7 °C 36/42 °C |
2.7 | 2.7 | 2.7 | 3.6 | 3.6 | 3.6 |
Weight | kg | 800 | 900 | 1000 | 1700 | 2400 | 2600 |
Performances calculated with the most suitable options and presented in accordance with EN 14511.
Oilon ChillHeat P150 – P450
Oilon ChillHeat P series heat pump uses energy efficient, reliable piston compressors to keep the operating and maintenance costs down.
- Max. hot water temperature 90 °C
- Combined cooling and heating
- Large residential buildings 5,000-15,000 m² or industrial process
Description/Model | P150 | P220 | P300 | P380 | P450 | |
---|---|---|---|---|---|---|
No. of Compressors compressor type |
2 piston |
3 piston |
4 piston |
5 piston |
6 piston |
|
Refrigerant | R134A | R134A | R134A | R134A | R134A | |
Heat output, kW (ground source heating) |
EN 14511 0/35 °C |
145 | 218 | 290 | 363 | 435 |
COP | EN 14511 0/35 °C |
4.0 | 4.0 | 4.0 | 4.0 | 4.0 |
Heat output, kW (heating network) |
18/8 °C 40/55 °C |
197 | 296 | 395 | 493 | 592 |
COP | 18/8 °C 40/55 °C |
3.7 | 3.7 | 3.7 | 3.7 | 3.7 |
Heat output, kW (Heating network, High temp) |
18/8 °C 55/75 °C |
159 | 238 | 317 | 396 | 475 |
COP | 18/8 °C 55/75 °C |
2.7 | 2.7 | 2.7 | 2.7 | 2.7 |
Cooling output, kW (air conditioning) |
12/7 °C 36/42 °C |
157 | 234 | 313 | 391 | 469 |
COPc | 12/7 °C 36/42 °C |
3.4 | 3.4 | 3.4 | 3.4 | 3.4 |
Weight | kg | 1600 | 2300 | 2600 | 3100 | 3700 |
Performances calculated with the most suitable options and presented in accordance with EN 14511.
Oilon ChillHeat S180 – S2000
Oilon ChillHeat S series heat pumps are equipped with energy efficient, reliable rotary compressors.
- Max. hot water temperature 67 °C
- Combined cooling and heating
- Large residential buildings 5,000-25,000 m² or industrial process
Description/Model | S180 | S280 | S380 | S490 | S600 | S800 | S1000 | S1200 | S1500 | S2000 | |
---|---|---|---|---|---|---|---|---|---|---|---|
No. of Compressors compressor type |
1 screw |
1 screw |
1 screw |
1 screw |
2 screw |
2 screw |
2 screw |
2 screw |
2 screw |
2 screw |
|
Refrigerant | R134A | R134A | R134A | R134A | R134A | R134A | R134A | R134A | R134A | R134A | |
Heat output, kW (ground source heating) |
EN 14511 0/35 °C |
191 | 300 | 404 | 516 | 638 | 889 | 1105 | 1306 | 1697 | 2298 |
COP | EN 14511 0/35 °C |
4.1 | 4.2 | 4.3 | 4.4 | 4.2 | 4.3 | 4.4 | 4.4 | 4.4 | 4.4 |
Heat output, kW (heating network) |
18/8 °C 40/55 °C |
241 | 379 | 506 | 665 | 740 | 1032 | 1283 | 1516 | 1971 | 2668 |
COP | 18/8 °C 40/55 °C |
3.6 | 3.6 | 3.7 | 3.8 | 3.6 | 3.7 | 3.8 | 3.8 | 3.8 | 3.8 |
Heat output, kW (Heating network, High temp) |
18/8 °C 50/65 °C |
226 | 364 | 473 | 623 | 729 | 1014 | 1259 | 1488 | 1934 | 2619 |
COP | 18/8 °C 50/65 °C |
2.7 | 2.8 | 2.9 | 3.0 | 2.8 | 2.9 | 3.0 | 3.0 | 3.0 | 3.0 |
Cooling output, kW (air conditioning) |
12/7 °C 36/42 °C |
201 | 315 | 394 | 549 | 696 | 971 | 1211 | 1432 | 1862 | 2521 |
COPc | 12/7 °C 36/42 °C |
3.6 | 3.6 | 3.7 | 3.8 | 3.6 | 3.7 | 3.8 | 3.8 | 3.8 | 3.8 |
Weight | kg | 2300 | 2900 | 3600 | 4000 | 3700 | 4500 | 5300 | 5900 | 7800 | 10400 |
Performances calculated with the most suitable options and presented in accordance with EN 14511.